14 ETHM-1 Plus SATEL
Name – name of the macro command group (up to 8 characters). It is presented on the
macro key.
Add macro – button available after you click on a macro command group. Clicking on the
button will display a list of defined macro commands. Click on the name to add the macro
command to the group.
Remove macro – click on the button to delete the selected macro command from the group.
– click on the button to move the highlighted macro command down within the group.
– click on the button to move the highlighted macro command up within the group.
Read – click on the button to read the macro command related data from the module.
Write – click on the button to write the macro command related data to the module.
Quit – click on the button to cancel reading or writing the macro command related data.
Reset – click on the button to delete all the defined macro commands (and restore factory
default settings).
Export to file – click on the button to export defined macro commands to a file. The file with
macro commands can be loaded into the MOBILEKPD-2 PRO application or imported to
another ETHM-1 Plus module or to a INT-KSG keypad (i.e. macro commands can be
copied between the devices).
Import from file – click on the button to import macro commands from a file.
6.4.2 Definitions
Macro commands can be created and configured in the "Definitions" tab. The macro
command is a sequence of actions, composed of single commands, which are to be done by
the control panel when running the macro command.
New macro – click on the button to create a new macro command.
Remove macro – click on the button to remove the selected macro command.
Name – individual macro command name (up to 32 characters).
Code – the code which is to be used for authorization when executing commands contained
in the macro command. The code must have an appropriate authority level for execution of
such commands to be possible. The code is presented as a string of asterisks.
If the code turns out to be incorrect when running macro commands (e.g. it was
changed in the meantime), the user will be able to enter the correct code. It will be
automatically saved to the phone memory (to replace the invalid code).
Authorization required – if this option is enabled, the macro command will only be run after
user authorization by means of code. The code entered in the "Code" field will be ignored.
Disabl. if armed – if this option is enabled, the macro command will not be available, if any
of the partitions managed by the virtual keypad is armed.
Autoexecute – if this option is enabled and there is only one macro command in the group,
the macro command will be run immediately on tapping the macro key (if the
A
UTHORIZATION REQUIRED option is enabled, user authorization by means of code will be
required).
Commands list – commands assigned to the currently highlighted macro command. The
and buttons allow you to change the order of commands (moving the
highlighted command up and down).
Add – click on the button to add to the list a new command, selected in the "Command" field.